LT PVC ARMOURED & UN-ARMOURED POWER CABLE

PRODUCT CONSTRUCTION


STANDARDS

IS:1554(P-1)-1988, IS:8130-1984, IS:5831-1984,IS:3975-1999


CONDUCTOR

The most acceptable metals are copper and Aluminium due to their higher conductivity & ductility. As Copper has got higher affinity for sulphur, it corrodes in the atmosphere where sulphur fumes are present. In these conditions tinned copper should be used. Aluminium oxide film which is always present on aluminum conductor surface acts as barrier and it protects the Aluminum conductor from corrosion in fumes laden atmosphere.


CONDUCTOR CONSTRUCTION

The most economical construction for conductor is stranded conductor. The strands are arranged in spiral layers in 1+6+12+18+…… formations. This construction provides more flexibility. Where crimping of lugs is required, the conductor has to be of stranded construction only. To economies in insulating material, weight and overall diameter, shaped conductors are employed in bigger sized cables. Here the stranded conductor is shaped in to a segment of a circle so that when all the cores are laid, they form a complete circle. These segments are identified as 2 Core- 180 degrees, 3 Core- 120 degrees, 4 Core- 90 degrees, 3.5 Core- 100/60 degrees.


INSULATION

The PVC covering over conductor is called insulation and is provided by extrusion process only. The insulated conductor is called core. IS-1554 permits two types of PVC insulation as follows:

  • Insulation with type A PVC Compound as per IS: 5831 which is suitable for 70°C continuous operation

  • Insulation with type C PVC Compound as per IS: 5831 which is suitable for 85°C continuous operation.


LAYING UP

The cores are laid up with suitable lay. The final layer always has a right hand lay i.e. if you look along the cable, the cores move to your right hand.


INNER SHEATH

Inner sheath is provided over the laid up cores. It is provided to give circular shape to the cable and it provides bedding for the armouring.

IS-1554 permits following two methods of applying the inner sheath of any thermoplastic material i.e. PVC, Polyethylene, etc.


  • Extruded Inner Sheath: Here the inner sheath is provided by extrusion of Thermoplastic over the laid up cores. This type of the inner sheath also acts as a water barrier between cores and outer sheath. Is case of a puncture in the outer sheath the water cannot reach to the cores and hence we recommend that cables for outdoor underground uses should have extruded inner sheath.

  • Tapped Inner Sheath: Here the inner sheath is provided by wrapping a thermoplastic tape over the laid up cores.


This method saves a process and hence manufactures always provide this type of inner sheath unless the purchase specifications ask for extruded inner sheath.


ARMOURING

In case of armoured cables, generally galvanized steel wire / strip is provided over the inner sheath is multi core cables and Aluminum Round wire or Aluminium strip over the insulation in single core cables. It provides mechanical protection inside cores and it carries earth return current in case of short circuit of a core with armour.

As per IS-1554 (Part-1) 1988, round wire armouring is provided in cable, where calculated diameter under armour is upto 13 mm. Above this the armouring is either with round wire or strip of size 4 mm 0.80 mm. As strip construction is economical, the manufactures always provide steel strip armouring unless wire armouring is specially specified.


In long run of cables and in case of mines, round wire armouring is must, as strip construction provide higher resistance to earth fault current and sometimes this current may not be sufficient to operate the circuit breaker in case of earth fault.


In mines, the resistance of the armour in no case should exceed the resistance of the main core by more than 33% for safety reasons. To achieve this, sometimes tinned hard drawn copper wires are required to be used along with galvanized steel wires. Sometimes two layers of Round steel wire or Steel Strip are applied in opposite direction with barrier tape in between are provided to give extra protection.


In case of single core for use in AC circuits, the material for armouring has to be non magnetic, as in this case the return current is not passing through the same cable and hence it will not cancel the magnetic lines produced by the current. These magnetic lines which are oscillating in case of AC current will give rise to eddy current in magnetic armouring and hence armouring will become hot, and this may lead to the failure of the cable. Generally hard drawn aluminum wires / strip are used for armouring in this case.


OUTER SHEATH

The PVC covering the armouring in case of armoured cables and over the inner sheath in case of un-armoured cables is called outer sheath. IS-1554 specifies nominal and minimum thickness of outer sheath for un–armoured cables and only minimum thickness of outer sheath for armoured cables.


It permits the following types of outer sheath PVC compounds:

  • Outer sheath with type ST1 PVC compound as per IS: 5831, which is suitable for 70°C continuous operation.

  • Outer sheath with type ST2 PVC compound as per IS: 5831, which is suitable for 85°C continuous operation.


PVC has got fire retardant properties due to its halogen content. The fire in the cable gets extinguished immediately on removal on the fire source.


In the modern Power, Chemical, Fertilizer and Cement plants many PVC cables are bunched in the cable shaft or on cable trays. In case of fire in these cables, the fire becomes self sustaining. Moreover due to the burning of PVC a dense corrosive smoke is emitted which makes fire fighting very difficult, due to poor visibility and toxic nature of the smoke. HCL content of the smoke, not only damages other costly equipment lying nearby, but also penetrates the RCC and corrodes the steel reinforcement. Due to this there is an extensive to the property.


To overcome these deficiencies FRLS i.e. Fire Retardant Low Smoke PVC was developed. If required, we can provide Fire Retardant Low Smoke (FRLS) PVC Inner Sheath and / or outer sheath. This PVC compound, apart from meeting the requirements of Type ST2 as per IS-5831, has got better fire retardant properties and it emits lower smoke and acid fumes when it catches fire.

​​​​​​​

The name Pioneer, year of manufacture & size are embossed on the outer sheath of the cable and at regular intervals as well as the meter marking has done with printer. Any other necessary information required by the customer’s is also embossed.